AWWA WQTC65857 Digital PDF

$14.00

Simultaneous Recovery of Diverse Microbes from Tap Water Using Hollow-Fiber Ultrafiltration
Conference Proceeding by American Water Works Association, 11/01/2007

Document Format: PDF

Description

This powerpoint presentation begins by providing a brief overview of simultaneous microbe concentrationfrom high volume samples, including charge modified microfilters, microfiltration for simultaneousmicrobe recovery, ultrafiltration (UF), and 100-L UF research. Conclusions were that:achieved simultaneous recovery of diversemicrobes from 100-L tap water samples;average UF recovery efficiencies from 45-89%;PCR detection at levels of 100 oocysts, cfuor pfu when 4-7% of water sample assayed;Cost – Capital: ~$2500, Supplies: ~$65; Blocking and Backflushing or Elution arean important part of the UF protocol;Backflushing augmented the recovery by 12 to 25%;Elution changed recovery by -6 to +22%;Two methods not significantly different; and,UF technique gaining visibility as aneffective and time-efficient technique forrecovering microbes from water. Includes 6 references, tables, figures.

Product Details

Edition:
Vol. – No.
Published:
11/01/2007
Number of Pages:
24
File Size:
1 file , 400 KB
Note: